Search this site
 
  Telemetry
 
  Telemetry Applications
 
  News:
 
 
Series 4 & 9
Series 9
  • PSTN or private wire
  • Line combiner option to combine up to three units connected to a single telephone line
  • Three input versions: 16 digital or 8 digital + 8 analogue, or 24 digital + 8 analogue
  • Digital inputs: 12-240V ac or dc = signal on; les than 12V = signal off; volt free contact closed = signal on; open circuit = signal off
  • Analogue outputs: 0-2v, 0-20mA, potentiometer (2k max)
  • Three phase failure dection: when any phase is less than 70% of nominal, or direction of phases is incorrect
  • Interface options: PSTN 300 or 1200 baud, TG5 IMS software, Vodaphone or BT message pagers
  • Control outputs from master station

Info
 · PDF
 · Manual
Series 9
Specification