D716x The D716x family
The D716x family is a range of IP65 Ultra low-power data logger/telemetry
outstations with optional low power GSM communication. Two power options are
available. The D7160 variant uses alkaline batteries that power the unit for up
to 7 years, depending on usage and temperature conditions. |
|
|
 |
D7160ex The D7160 ex is designed for
monitoring small I/O in explosive atmospheres when mains power is not suitable
but the functionality and communication of an outstation / RTU is still
required. The D7160 ex series fits Combined Sewer Overflow (CSO)
monitoring. |
|
 |
 |
D715x The D715x family
is a range of IP65/IP67 low-power data logger/telemetry outstations. Three
power options are available: the D7150 variant uses alkaline batteries that
power the unit for up to 5 years, depending on usage and temperature
conditions. The unit is available in a dc-powered (D7151) or mains ac-powered
(D7155) configuration with internal battery back-up. The many capabilities and
small size of the D715x means that it is ideally suited to a wide range of
applications in the utilities and industrial markets. |
|
 |
 |
D714x The D714x family
is a range of IP65/IP67 low-power data logger/telemetry outstations. Three
power options are available: the D7140 variant uses alkaline batteries that
power the unit for up to 5 years, depending on usage and temperature
conditions. The unit is available in a dc-powered (D7141) or mains ac-powered
(D7145) configuration with internal battery back-up The many capabilities and
small size of the D714x means that it is ideally suited to a wide range of
applications in the utilities and industrial markets. |
|
 |
 |
D711x Welcome to the
D711x bus- based outstation, a wide range of I/ O modules can be fitted
allowing for a flexible amount of I/ O, and ideally suited where 25 - 512
inputs (subject to type) are to be monitored, logged and alarmed. In addition,
the unit can cater for a whole range of communications available over the D7000
Series. |
|
 |
 |
D4150/60 The D4150 and
D4160 series of outstations are small (190 mm W x 190mm H x 130mm D) low-cost,
ultra low power programmable logging stations. These high versatile products
can be used as telemetry outstations or as stand-alone loggers with a battery
life of up to 10 years. Comes with a choice of power supplies and optional
facilities to fit a wide variety of applications and needs. They are ideal for
smaller I/O sites requiring typically 2 - 6 digital inputs and 2 - 4 analogue
inputs, with 2 - 4 digital outputs. With the option of submersible
(IP68). |
|
 |
 |
D4140 - GSM The GSM
interface is a seamless upgrade for those sites which do not have either PSTN
or licensed radio facilities, perhaps because of cost and/or access. The GSM
unit has been designed to operate with most networks on the market. The
electronics inside enable the GSM to remain powered, thereby maintaining its
position on the cheapest network. The alternative powering up the GSM
when an alarm dial-out is generated may not guarantee a connection when
needed and may require the use of a pager to 'wake up' the GSM unit, adding
extra cost to the installation. |
|
 |
 |
D4140 - D4141/45 The D4140
is a compact (305mm H x 190mm W x 130mm D) battery powered outstation providing
flexible data monitoring with a range of different inputs including digitals,
analogues, shaft encoders and BCD, as well as digital outputs. Supplied in an
IP67 environmental enclosure allowing operation in harsh conditions. GSM
Option available. |
|
 |
 |
D6000 Combines
sophisticated level and pump control with full telemetry and pump status
monitoring to provide all the data needed to reduce pump and process downtime.
Dial-out to radio pager (or host) allows efficient alarm reporting and rapid
maintenance response. |
|
 |
 |
D1234/36 This is an
entry level Microlog, providing 16 digital inputs, 4 analogue inputs, and 2
count inputs in a compact enclosure (300mm W x 300mm H x 180mm D). The D1234
can be expanded to include simple data logging and digital outputs.
|
|
 |
 |
D4110 The D4110 is a
medium sized (360mm H x 540mm W x 240mm D) intelligent programmable outstation.
As this is a bus-based outstation, a wide range of I/O cards can be fitted
allowing for a flexible amount of I/O, and ideally suited where 20 - 100 inputs
(subject to type) are to be monitored. In addition, the unit can cater for dual
communications, ie. private wire with PSTN fallback. |
|
 |
 |
Series 4
- Digital inputs: 12-240V ac or dc =
signal on; less than 12V = signal off
- Interface options: PSTN 300 or 1200
baud, TG5 IMS software, Vodaphone or BT message pagers
- Two versions: 16 digital + 4
analogue or 8 digital + 8 analogue
- Visual indication of digital input
status and power
|
|
 |
 |
Series 8 and 9
- PSTN or private wire
- Line combiner option to combine up
to three units connected to a single telephone line
- Three input versions: 16 digital or
8 digital + 8 analogue, or 24 digital + 8 analogue
- Digital inputs: 12-240V ac or dc =
signal on; les than 12V = signal off; volt free contact closed = signal on;
open circuit = signal off
- Analogue outputs: 0-2v, 0-20mA,
potentiometer (2k max)
- Three phase failure dection: when
any phase is less than 70% of nominal, or direction of phases is
incorrect
- Interface options: PSTN 300 or 1200
baud, TG5 IMS software, Vodaphone or BT message pagers
- Control outputs from master
station
|
|
 |
 |
TG1150
- 4 cards slots
- Complete range of daughter
cards
- Long battery life (up to three
years) from six standard alkaline D cells
- Secure data transmission
- Remote configuration with add-on
card
- Alarm dial out on change of state,
when: programmed values, pulse counts, count calculations or data base capacity
are exceeded or when programmed logical combinations are met
- Main powered with Ni. Cad
rechargable cells, as alternative build
- Control outputs initiated from the
master station
|
|